0.6/1kv Low Voltage Underground Copper/Aluminum Conductor XLPE Insulated PVC Sheathed Steel Wire Armoured Power Cable
وصف
تخصيص
وصف المنتج
Low Voltage Cable
1. تطبيق
The cable is used in electric transmission and distribution system operating at AC rated voltage up to and including 1.8/3 KV
2. Operating Characteristic
1) The rated voltage U0/U of cable is 0.6/1KV.
2) The long time allowable working temperature of conductor is 70 °C FOR cable with PVC insulation, 90 °C for cable with XLPE insulation.
3) The cable laying temperature is not less than 0°C, and the allowable bending radius of a cable is not less 20 times than cable overall diameter for single core unarmored cable, 15 times of that for single core armored, 12 times of that for 3 cores armored cable.
1. Scope
The cables are manufactured and tested in accordance with IEC60502 Power Cables with Extruded Insulation and their accessories for rated voltages from 1kV(Um1.2 kV) up to 30kV(Um 36kV). Whereas, Greatwall كابل can supply XLPE insulation cables according to other recognized national and international standards or customized تخصيص.
2. Construction and Material
1) موصل
Conductors are normally class 2 of compacted cicular or circular standard conductors of copper or aluminium.
2) Conductor Screen
All cable of rated voltage above 1.8/3kV are supplied with conductor screening which is non-mهntallic and consists of either semi-conducting tape or a layer of extruded semi-conducting compound,or a combination of the two.
3) Insulation
Insulation is a layer of extruded cross-linked polyethylene(XLPE).
4) Insulation Screen
For cable at rated voltage above 1.8/3kV ,insulation screening consists of a non-metallic semi-conducting part in combination with a metallic layer and consists of either semi-conducting tape or a layer of extruded semi-conducting compound.. The extruded insulation screen is normally free strippable(easy removable) type but can be provided with bonded one upon request.
The metallic part is normally applied on the individual cores for rated voltage above 1.8/3kV and on the core assembly for rated voltage 1.8/3kV and consists of plain annealed copper tape. or copper tape screen a layer of copper wire,a lead alloy or corrugated aluminum sheath can be provided upon request.
5) Inner Covering or Separation Sheath
(for armored cables)
A layer of PVC inner coveing is applied under the armor ,if there is no screen.
When the metallic screening and the armor are of different metals, an extruded separation sheath of PVC is provided in order to separate the different metals.
6) Metallic Armor
The armor, if required, consists of single layer of round wires or double tapes of galvanized steel or aluminum or other non-magnetic metals. Single core cables are normally armored with aluminum(other non-magnetic metals), because non-magnetic armor is essential for single core cable for use on A.C circuit .
7) Outer Sheath
All cable are normally provided with an extruded PVC out sheath, black colored(class ST2). Other materials can be available upon request,as PE , polyethylene,high flame or fire retardant PVC and etc.
8) Core Identification
The multiple conductors are identified as according IEC60502 .
Cable Marking(حسب الطلب)
The following information are indicated on the surface of the outer sheath. However, the marking can also be customized.
—-voltage rating, area for cable
—-manufacturer’s name
—-year of manufacturer
—-lengther for cable
—-إلخ
3.Typical Drawing
PARAMETERS
Cores and Nominal Cross Section Area: | |||||||||||
Rated voltage 0.6/1kV Single core Basic parameter of Power Cable | |||||||||||
Nominal cross sectionmm2 | Thickness of insulationmm | CU/XLPE/PVC;AL/XLPE/PVC | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
Thickness of sheathmm | Approx. overall diameter of cable mm | CU/XLPE/PVC | AL/XLPE/PVC | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | CU/XLPE/SWA/PVC | AL/XLPE/SWA/PVC | ||
1.5 | 0.7 | 0.7 | 5.6 | 45 | 35 | ||||||
2.5 | 0.7 | 0.7 | 6 | 56 | 41 | ||||||
4 | 0.7 | 0.7 | 6.5 | 74 | 49 | ||||||
6 | 0.7 | 0.7 | 7 | 95 | 59 | ||||||
10 | 0.7 | 0.7 | 8.2 | 139 | 79 | ||||||
16 | 0.7 | 0.7 | 9.1 | 197 | 102 | ||||||
25 | 0.9 | 0.9 | 10.6 | 293 | 143 | 0.9 | 0.2 | 1.8 | 14 | 451 | 301 |
35 | 0.9 | 0.9 | 11.6 | 386 | 178 | 0.9 | 0.2 | 1.8 | 15 | 558 | 349 |
50 | 1 | 1 | 13 | 507 | 225 | 0.9 | 0.2 | 1.8 | 16.4 | 698 | 416 |
70 | 1.1 | 1.1 | 14.9 | 708 | 300 | 0.9 | 0.2 | 1.8 | 18.3 | 926 | 519 |
95 | 1.1 | 1.1 | 16.8 | 959 | 394 | 0.9 | 0.2 | 1.8 | 20 | 1194 | 628 |
120 | 1.2 | 1.2 | 18.5 | 1193 | 479 | 0.9 | 0.2 | 1.8 | 21.7 | 1450 | 737 |
150 | 1.4 | 1.4 | 20.6 | 1470 | 590 | 0.9 | 0.2 | 1.8 | 23.6 | 1745 | 865 |
185 | 1.6 | 1.6 | 22.8 | 1831 | 730 | 0.9 | 0.2 | 1.8 | 25.6 | 2122 | 1021 |
240 | 1.7 | 1.7 | 25.7 | 2380 | 933 | 0.9 | 0.2 | 1.9 | 28.5 | 2706 | 1259 |
300 | 1.8 | 1.8 | 28.3 | 2960 | 1144 | 0.9 | 0.2 | 1.9 | 30.9 | 3304 | 1488 |
400 | 2 | 2 | 31.3 | 3755 | 1433 | 1.2 | 0.5 | 2.1 | 35.9 | 4494 | 2173 |
Rated voltage 0.6/1kV Two cores Basic parameter of Power Cable | |||||||||||
Nominal cross sectionmm2 | Thickness of insulationmm | CU/XLPE/PVC,AL/XLPE/PVC | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
Thickness of sheathmm | Approx. overall diameter of cable mm | CU/XLPE/PVC | AL/XLPE/PVC | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | CU/XLPE/SWA/PVC | AL/XLPE/SWA/PVC | ||
1.5 | 0.7 | 1.8 | 10.2 | 114 | 96 | 0.9 | 0.2 | 1.8 | 12.8 | 232 | 214 |
2.5 | 0.7 | 1.8 | 11 | 141 | 111 | 0.9 | 0.2 | 1.8 | 13.6 | 269 | 238 |
4 | 0.7 | 1.8 | 12 | 181 | 132 | 0.9 | 0.2 | 1.8 | 14.6 | 320 | 271 |
6 | 0.7 | 1.8 | 13 | 228 | 156 | 0.9 | 0.2 | 1.8 | 15.6 | 379 | 306 |
10 | 0.7 | 1.8 | 15.4 | 331 | 211 | 0.9 | 0.2 | 1.8 | 18 | 509 | 389 |
16 | 0.7 | 1.8 | 17.2 | 458 | 268 | 0.9 | 0.2 | 1.8 | 19.8 | 657 | 467 |
25 | 0.9 | 1.8 | 20.2 | 672 | 371 | 0.9 | 0.2 | 1.8 | 22.8 | 905 | 604 |
35 | 0.9 | 1.8 | 22.2 | 873 | 455 | 0.9 | 0.2 | 1.8 | 24.8 | 1130 | 712 |
50 | 1 | 1.8 | 25 | 1140 | 574 | 0.9 | 0.2 | 1.8 | 27.6 | 1428 | 863 |
70 | 1.1 | 1.9 | 29 | 1592 | 775 | 1.2 | 0.2 | 2 | 33.6 | 2262 | 1445 |
95 | 1.1 | 2 | 32.6 | 2134 | 1000 | 1.2 | 0.2 | 2.2 | 37.4 | 2899 | 1765 |
120 | 1.2 | 2.1 | 36.2 | 2660 | 1229 | 1.2 | 0.5 | 2.3 | 41 | 3504 | 2074 |
150 | 1.4 | 2.3 | 40.4 | 3287 | 1522 | 1.2 | 0.5 | 2.4 | 45 | 4202 | 2437 |
185 | 1.6 | 2.4 | 44.6 | 4073 | 1864 | 1.2 | 0.5 | 2.5 | 49.2 | 5079 | 2870 |
240 | 1.7 | 2.6 | 50.4 | 5287 | 2384 | 1.4 | 0.5 | 2.8 | 55.6 | 6457 | 3554 |
300 | 1.8 | 2.8 | 55.6 | 6567 | 2925 | 1.4 | 0.5 | 2.9 | 60.6 | 7822 | 4180 |
400 | 2 | 2.9 | 61.4 | 8279 | 3622 | 1.4 | 0.5 | 3.1 | 66.6 | 9692 | 5034 |
Rated voltage 0.6/1kV Three cores Basic parameter of Power Cable | |||||||||||
Nominal cross sectionmm2 | Thickness of insulationmm | CU/XLPE/PVC,AL/XLPE/PVC | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
Thickness of sheathmm | Approx. overall diameter of cable mm | CU/XLPE/PVC | AL/XLPE/PVC | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | CU/XLPE/SWA/PVC | AL/XLPE/SWA/PVC | ||
1.5 | 0.7 | 1.8 | 10.7 | 135 | 107 | 0.9 | 0.2 | 1.8 | 13.3 | 259 | 231 |
2.5 | 0.7 | 1.8 | 11.5 | 171 | 125 | 0.9 | 0.2 | 1.8 | 14.1 | 304 | 259 |
4 | 0.7 | 1.8 | 12.6 | 225 | 152 | 0.9 | 0.2 | 1.8 | 15.2 | 370 | 297 |
6 | 0.7 | 1.8 | 13.7 | 291 | 182 | 0.9 | 0.2 | 1.8 | 16.3 | 449 | 341 |
10 | 0.7 | 1.8 | 16.3 | 429 | 250 | 0.9 | 0.2 | 1.8 | 18.9 | 618 | 438 |
16 | 0.7 | 1.8 | 18.2 | 609 | 324 | 0.9 | 0.2 | 1.8 | 20.8 | 820 | 534 |
25 | 0.9 | 1.8 | 21.4 | 907 | 455 | 0.9 | 0.2 | 1.8 | 24 | 1154 | 703 |
35 | 0.9 | 1.8 | 23.6 | 1194 | 567 | 0.9 | 0.2 | 1.8 | 26.2 | 1466 | 840 |
50 | 1 | 1.8 | 26.6 | 1570 | 722 | 0.9 | 0.2 | 1.9 | 29.4 | 1891 | 1042 |
70 | 1.1 | 1.9 | 30.9 | 2208 | 983 | 1.2 | 0.2 | 2.1 | 35.7 | 2936 | 1711 |
95 | 1.1 | 2.1 | 35 | 2995 | 1294 | 1.2 | 0.5 | 2.2 | 39.6 | 3794 | 2093 |
120 | 1.2 | 2.2 | 38.8 | 3741 | 1595 | 1.2 | 0.5 | 2.4 | 43.6 | 4642 | 2496 |
150 | 1.4 | 2.3 | 43.1 | 4601 | 1953 | 1.2 | 0.5 | 2.5 | 47.9 | 5598 | 2950 |
185 | 1.6 | 2.5 | 47.8 | 5738 | 2425 | 1.4 | 0.5 | 2.7 | 53 | 6851 | 3538 |
240 | 1.7 | 2.7 | 54 | 7462 | 3107 | 1.4 | 0.5 | 2.9 | 59.2 | 8711 | 4356 |
300 | 1.8 | 2.9 | 59.6 | 9283 | 3820 | 1.4 | 0.5 | 3.1 | 64.8 | 10655 | 5192 |
400 | 2 | 3.1 | 66 | 11771 | 4786 | 1.4 | 0.5 | 3.3 | 71.2 | 13284 | 6299 |
Rated voltage 0.6/1kV Four cores Basic parameter of Power Cable | |||||||||||
Nominal cross sectionmm2 | Thickness of insulationmm | CU/XLPE/PVC,AL/XLPE/PVC | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
Thickness of sheathmm | Approx. overall diameter of cable mm | CU/XLPE/PVC | AL/XLPE/PVC | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | CU/XLPE/SWA/PVC | AL/XLPE/SWA/PVC | ||
1.5 | 0.7 | 1.8 | 11.4 | 160 | 123 | 0.9 | 0.2 | 1.8 | 14 | 292 | 255 |
2.5 | 0.7 | 1.8 | 12.4 | 207 | 147 | 0.9 | 0.2 | 1.8 | 15 | 351 | 290 |
4 | 0.7 | 1.8 | 13.6 | 277 | 179 | 0.9 | 0.2 | 1.8 | 16.2 | 434 | 337 |
6 | 0.7 | 1.8 | 14.8 | 362 | 217 | 0.9 | 0.2 | 1.8 | 17.4 | 533 | 389 |
10 | 0.7 | 1.8 | 17.7 | 542 | 302 | 0.9 | 0.2 | 1.8 | 20.3 | 746 | 507 |
16 | 0.7 | 1.8 | 19.8 | 777 | 396 | 0.9 | 0.2 | 1.8 | 22.4 | 1005 | 625 |
25 | 0.9 | 1.8 | 23.5 | 1169 | 566 | 0.9 | 0.2 | 1.8 | 26.1 | 1440 | 838 |
35 | 0.9 | 1.8 | 25.9 | 1546 | 710 | 0.9 | 0.2 | 1.9 | 28.7 | 1858 | 1022 |
50 | 1 | 1.9 | 29.5 | 2054 | 923 | 1.2 | 0.2 | 2.1 | 34.3 | 2751 | 1620 |
70 | 1.1 | 2.1 | 34.4 | 2909 | 1275 | 1.2 | 0.2 | 2.2 | 39 | 3695 | 2061 |
95 | 1.1 | 2.2 | 38.8 | 3930 | 1661 | 1.2 | 0.5 | 2.4 | 43.6 | 4831 | 2563 |
120 | 1.2 | 2.3 | 43.1 | 4913 | 2051 | 1.2 | 0.5 | 2.5 | 47.9 | 5909 | 3048 |
150 | 1.4 | 2.5 | 48 | 6067 | 2537 | 1.4 | 0.5 | 2.7 | 53.2 | 7184 | 3654 |
185 | 1.6 | 2.7 | 53.3 | 7566 | 3148 | 1.4 | 0.5 | 2.8 | 58.3 | 8772 | 4355 |
240 | 1.7 | 2.9 | 60.2 | 9839 | 4033 | 1.4 | 0.5 | 3.1 | 65.4 | 11225 | 5419 |
300 | 1.8 | 3.1 | 66.4 | 12242 | 4957 | 1.4 | 0.5 | 3.3 | 71.6 | 13764 | 6479 |
400 | 2 | 3.3 | 73.5 | 15526 | 6212 | 1.4 | 0.5 | 3.5 | 78.7 | 17205 | 7891 |
Rated voltage 0.6/1kV Five cores Basic parameter of Power Cable | |||||||||||
Nominal cross sectionmm2 | Thickness of insulationmm | CU/XLPE/PVC,AL/XLPE/PVC | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
Thickness of sheathmm | Approx. overall diameter of cable mm | CU/XLPE/PVC | AL/XLPE/PVC | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | CU/XLPE/SWA/PVC | AL/XLPE/SWA/PVC | ||
1.5 | 0.7 | 1.8 | 12.2 | 186 | 140 | 0.9 | 0.2 | 1.8 | 14.8 | 328 | 281 |
2.5 | 0.7 | 1.8 | 13.3 | 244 | 168 | 0.9 | 0.2 | 1.8 | 15.9 | 398 | 322 |
4 | 0.7 | 1.8 | 14.6 | 329 | 207 | 0.9 | 0.2 | 1.8 | 17.2 | 498 | 376 |
6 | 0.7 | 1.8 | 16 | 434 | 254 | 0.9 | 0.2 | 1.8 | 18.6 | 619 | 439 |
10 | 0.7 | 1.8 | 19.2 | 655 | 356 | 0.9 | 0.2 | 1.8 | 21.8 | 877 | 578 |
16 | 0.7 | 1.8 | 21.7 | 948 | 472 | 0.9 | 0.2 | 1.8 | 24.3 | 1199 | 723 |
25 | 0.9 | 1.8 | 25.7 | 1432 | 679 | 0.9 | 0.2 | 1.9 | 28.5 | 1742 | 989 |
35 | 0.9 | 1.9 | 28.6 | 1914 | 869 | 0.9 | 0.2 | 2 | 31.4 | 2257 | 1213 |
50 | 1 | 2 | 32.6 | 2546 | 1131 | 1.2 | 0.2 | 2.2 | 37.4 | 3310 | 1896 |
70 | 1.1 | 2.2 | 38.1 | 3607 | 1565 | 1.2 | 0.5 | 2.3 | 42.7 | 4473 | 2431 |
95 | 1.1 | 2.3 | 42.9 | 4876 | 2040 | 1.2 | 0.5 | 2.5 | 47.7 | 5868 | 3032 |
120 | 1.2 | 2.5 | 47.9 | 6120 | 2543 | 1.4 | 0.5 | 2.7 | 53.1 | 7235 | 3658 |
150 | 1.4 | 2.7 | 53.4 | 7556 | 3143 | 1.4 | 0.5 | 2.8 | 58.4 | 8765 | 4352 |
185 | 1.6 | 2.9 | 59.2 | 9419 | 3897 | 1.4 | 0.5 | 3 | 64.2 | 10752 | 5230 |
240 | 1.7 | 3.1 | 66.9 | 12249 | 4992 | 1.4 | 0.5 | 3.3 | 72.1 | 13783 | 6525 |
300 | 1.8 | 3.4 | 74 | 15273 | 6168 | 1.4 | 0.5 | 3.5 | 79 | 16925 | 7820 |
400 | 2 | 3.6 | 82 | 19369 | 7726 | 1.4 | 0.5 | 3.8 | 88.4 | 22080 | 10437 |
Rated voltage 0.6/1kV 3+1 cores Basic parameter of Power Cable | |||||||||||
Nominal cross sectionmm2 | Thickness of insulationmm | CU/XLPE/PVC,AL/XLPE/PVC | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
Thickness of sheathmm | Approx. overall diameter of cable mm | CU/XLPE/PVC | AL/XLPE/PVC | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | CU/XLPE/SWA/PVC | AL/XLPE/SWA/PVC | ||
2.5/1.5 | 0.7/0.7 | 1.8 | 12.4 | 198 | 143 | 0.9 | 0.2 | 1.8 | 15 | 342 | 287 |
4/2.5 | 0.7/0.7 | 1.8 | 13.6 | 262 | 174 | 0.9 | 0.2 | 1.8 | 16.2 | 420 | 332 |
64 | 0.7/0.7 | 1.8 | 14.8 | 343 | 211 | 0.9 | 0.2 | 1.8 | 17.4 | 515 | 382 |
106 | 0.7/0.7 | 1.8 | 17.7 | 506 | 290 | 0.9 | 0.2 | 1.8 | 20.3 | 710 | 495 |
1016 | 0.7/0.7 | 1.8 | 19.8 | 724 | 378 | 0.9 | 0.2 | 1.8 | 22.4 | 953 | 607 |
25/16 | 0.9/0.7 | 1.8 | 23.5 | 1083 | 536 | 0.9 | 0.2 | 1.8 | 26.1 | 1354 | 807 |
35/16 | 0.9/0.7 | 1.8 | 25.3 | 1371 | 649 | 0.9 | 0.2 | 1.9 | 28.1 | 1676 | 954 |
50/25 | 1.0/0.9 | 1.9 | 28.8 | 1852 | 853 | 0.9 | 0.2 | 2 | 31.6 | 2198 | 1199 |
70/35 | 1.1/0.9 | 2 | 33.5 | 2593 | 1158 | 1.2 | 0.2 | 2.2 | 38.3 | 3378 | 1944 |
95/50 | 1.1/1.0 | 2.2 | 37.9 | 3506 | 1522 | 1.2 | 0.5 | 2.3 | 42.5 | 4367 | 2383 |
120/70 | 1.2/1.1 | 2.3 | 42.1 | 4452 | 1897 | 1.2 | 0.5 | 2.5 | 46.9 | 5425 | 2871 |
150/70 | 1.4/1.1 | 2.5 | 46.9 | 5361 | 2305 | 1.4 | 0.5 | 2.6 | 51.9 | 6430 | 3373 |
185/95 | 1.6/1.1 | 2.6 | 51.8 | 6732 | 2851 | 1.4 | 0.5 | 2.8 | 57 | 7933 | 4053 |
240/120 | 1.7/1.2 | 2.9 | 58.8 | 8740 | 3670 | 1.4 | 0.5 | 3 | 63.8 | 10065 | 4995 |
300/150 | 1.8/1.4 | 3.1 | 64.8 | 10850 | 4504 | 1.4 | 0.5 | 3.2 | 69.8 | 12304 | 5958 |
400/185 | 2.0/1.6 | 3.3 | 71.8 | 13718 | 5628 | 1.4 | 0.5 | 3.5 | 77 | 15359 | 7269 |
Rated voltage 0.6/1kV 3+2 cores Basic parameter of Power Cable | |||||||||||
Nominal cross sectionmm2 | Thickness of insulationmm | CU/XLPE/PVC,AL/XLPE/PVC | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
Thickness of sheathmm | Approx. overall diameter of cable mm | CU/XLPE/PVC | AL/XLPE/PVC | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | CU/XLPE/SWA/PVC | AL/XLPE/SWA/PVC | ||
2.5/1.5 | 0.7/0.7 | 1.8 | 13.3 | 225 | 161 | 0.9 | 0.2 | 1.8 | 15.9 | 379 | 315 |
4/2.5 | 0.7/0.7 | 1.8 | 14.6 | 300 | 197 | 0.9 | 0.2 | 1.8 | 17.2 | 469 | 366 |
64 | 0.7/0.7 | 1.8 | 16 | 398 | 241 | 0.9 | 0.2 | 1.8 | 18.6 | 583 | 426 |
106 | 0.7/0.7 | 1.8 | 19.2 | 584 | 332 | 0.9 | 0.2 | 1.8 | 21.8 | 806 | 554 |
1016 | 0.7/0.7 | 1.8 | 21.8 | 844 | 439 | 0.9 | 0.2 | 1.8 | 24.4 | 1096 | 691 |
25/16 | 0.9/0.7 | 1.8 | 25.7 | 1262 | 620 | 0.9 | 0.2 | 1.9 | 28.5 | 1572 | 930 |
35/16 | 0.9/0.7 | 1.8 | 27.5 | 1557 | 740 | 0.9 | 0.2 | 1.9 | 30.3 | 1889 | 1072 |
50/25 | 1.0/0.9 | 2 | 31.6 | 2148 | 998 | 1.2 | 0.2 | 2.1 | 36.2 | 2873 | 1724 |
70/35 | 1.1/0.9 | 2.1 | 36.7 | 2993 | 1350 | 1.2 | 0.2 | 2.3 | 41.5 | 3849 | 2206 |
95/50 | 1.1/1.0 | 2.3 | 41.5 | 4037 | 1770 | 1.2 | 0.5 | 2.4 | 46.1 | 4976 | 2709 |
120/70 | 1.2/1.1 | 2.4 | 46.1 | 5186 | 2223 | 1.4 | 0.5 | 2.6 | 51.3 | 6262 | 3299 |
150/70 | 1.4/1.1 | 2.6 | 51.5 | 6133 | 2669 | 1.4 | 0.5 | 2.8 | 56.7 | 7328 | 3863 |
185/95 | 1.6/1.1 | 2.8 | 57.1 | 7789 | 3341 | 1.4 | 0.5 | 3 | 62.3 | 9106 | 4658 |
240/120 | 1.7/1.2 | 3 | 64.5 | 10040 | 4255 | 1.4 | 0.5 | 3.2 | 69.7 | 11521 | 5736 |
300/150 | 1.8/1.4 | 3.3 | 71.3 | 12479 | 5251 | 1.4 | 0.5 | 3.4 | 76.3 | 14074 | 6845 |
400/185 | 2.0/1.6 | 3.5 | 79 | 15742 | 6547 | 1.4 | 0.5 | 3.7 | 85.4 | 18358 | 9163 |
Rated voltage 0.6/1kV 4+1 cores Basic parameter of Power Cable | |||||||||||
Nominal cross sectionmm2 | Thickness of insulationmm | CU/XLPE/PVC,AL/XLPE/PVC | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
Thickness of sheathmm | Approx. overall diameter of cable mm | CU/XLPE/PVC | AL/XLPE/PVC | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | CU/XLPE/SWA/PVC | AL/XLPE/SWA/PVC | ||
2.5/1.5 | 0.7/0.7 | 1.8 | 13.3 | 235 | 165 | 0.9 | 0.2 | 1.8 | 15.9 | 389 | 319 |
4/2.5 | 0.7/0.7 | 1.8 | 14.6 | 315 | 202 | 0.9 | 0.2 | 1.8 | 17.2 | 483 | 371 |
64 | 0.7/0.7 | 1.8 | 16 | 416 | 247 | 0.9 | 0.2 | 1.8 | 18.6 | 601 | 432 |
106 | 0.7/0.7 | 1.8 | 19.2 | 620 | 344 | 0.9 | 0.2 | 1.8 | 21.8 | 842 | 566 |
1016 | 0.7/0.7 | 1.8 | 21.7 | 896 | 455 | 0.9 | 0.2 | 1.8 | 24.3 | 1146 | 706 |
25/16 | 0.9/0.7 | 1.8 | 25.7 | 1347 | 650 | 0.9 | 0.2 | 1.9 | 28.5 | 1657 | 960 |
35/16 | 0.9/0.7 | 1.9 | 28.2 | 1742 | 811 | 0.9 | 0.2 | 1.9 | 30.8 | 2067 | 1136 |
50/25 | 1.0/0.9 | 2 | 32.1 | 2347 | 1065 | 1.2 | 0.2 | 2.1 | 36.7 | 3083 | 1802 |
70/35 | 1.1/0.9 | 2.2 | 37.5 | 3308 | 1466 | 1.2 | 0.5 | 2.3 | 42.1 | 4161 | 2318 |
95/50 | 1.1/1.0 | 2.3 | 42.2 | 4456 | 1905 | 1.2 | 0.5 | 2.5 | 47 | 5432 | 2881 |
120/70 | 1.2/1.1 | 2.5 | 47.1 | 5663 | 2394 | 1.4 | 0.5 | 2.6 | 52.1 | 6736 | 3466 |
150/70 | 1.4/1.1 | 2.7 | 52.6 | 6857 | 2918 | 1.4 | 0.5 | 2.8 | 57.6 | 8048 | 4109 |
185/95 | 1.6/1.1 | 2.8 | 58.1 | 8591 | 3606 | 1.4 | 0.5 | 3 | 63.3 | 9931 | 4946 |
240/120 | 1.7/1.2 | 3.1 | 65.8 | 11159 | 4638 | 1.4 | 0.5 | 3.3 | 71 | 12668 | 6146 |
300/150 | 1.8/1.4 | 3.3 | 72.6 | 13860 | 5693 | 1.4 | 0.5 | 3.5 | 77.8 | 15518 | 7351 |
400/185 | 2.0/1.6 | 3.6 | 80.6 | 17573 | 7154 | 1.4 | 0.5 | 3.8 | 87 | 20238 | 9819 |
4. Tests
The finished cables meet all the appropriate test requirments specified in IEC60502.
1 Information
أ, Number of cores:
1, 2, 3, 3+1, 3+2, 3+3, 4, 4+1, 4+2, 5 وما إلى ذلك وهلم جرا.
b, Construction:
موصل: Solid or stranded copper
Insulation: Cross-linked polyethylene (XLPE) or Polyvinyl chloride (PVC)
Filler: Polypropylene filament with lapped binding tape
Binder: Binding tape
Inner sheath: Polyvinyl chloride (PVC)
Armor: Galvanized steel wire armored(SWA) or steel tape armored(STA)
Sheath: Polyvinyl chloride (PVC)
c, Nominal Section
Area(mm2) :1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800
d, سمات
XLPE insulated power cable does not have excellent electric, mechanical properties, but also has powerful resistance against chemical corrosion, heat resistance and environmental stress resistance. Its structure is simple. The long period operating temperature is +90 °C. It is convenient to use and can be laid with no restriction on different levels.
XLPE insulated steel wire armored power cable: XLPE/PVC insulated power cable has a number of advantages over paper insulated and PVC insulated cable. XLPE cable has high electric strength, mechanical strength, high-aging resisting, environmental stress resisting antichemical corrosion, and it is a simple construction, using convenient and higher operating of long term temperature. It can be laid with no drop restriction.
Various flame-retardant and non-flame retardant XLPE cable can be manufactured with three technology(peroxide, silane and irradiation cross-linking). The flame-retardant cable covers all kinds of low-smoke low-halogen low-smoke halogen-free, and non-smoke nonhalogenated and three classes of A, ب, ج.
2 معيار:
IEC60502,and BS6346, VDE, AS/NZS, UL,etc or as customer’s request.
3 The Rated Voltage(kv):
1st class 0.6/1 1.8/3 3.6/6 6/10 8.7/15 12/20 18/30 21/35
2nd class 1/1 3/3 6/6 8.7/10 12/15 18/20 – 26/35
4 تطبيق:
1)These cables are most suitable for direct burial or for installation on trays or ducts, Where there is
risk of mechanical damage, armored cables should be used.
2) For laying in the ground along the route with large difference of level able to bear external mechanical forces.
3.Typical Drawing
4. Tests
The finished cables meet all the appropriate test requirments specified in IEC60502.
5.Packing
Range of Business:
Cables
Low Voltage Power Cable: 0.6/1kV and Below PVC or XLPE Insulated Power Cable
Medium Voltage Power Cable: 6-35kV XLPE Insulated Power Cable
High Voltage (Extra-high Voltage) سلك الطاقة: 66-500kV XLPE Insulated Power Cable
Bare Conductor and Electrical Wires
Cable Accessories
1~35kv cold shrinkable products
أ. Indoor termination
b. Outdoor termination
c. Straight Through Joint
1~35kv heat shrinkable Products
أ. Indoor termination
b. Outdoor termination
c. Straight Through Joint
66kv ~500kv Products
أ. Porcelain Outdoor termination
b. Compound Sleeve Termination
c. GIS termination ( Assembly, plug-in Type )
d. Premould termination
ه. Straight Joint/ Insulation Joint
f. Branch Joint
ز. Dry and Y shape Branch Joint
دبليوhy choose us?
- Export to many countries including Iraq, Tanzania and Australia and USA.
- Best manufacturing and testing equipments imported from Germany, USA and Japan guarantee the best quality with competitive prices.
- Professional overseas team guarantees you best pre-and-after sale services.
- Experienced engineers and workers for more than 20 years ensure the quality and customized products.
- 5S Management to enhance the qualifications of staff and make better service for customers.
- Near Shanghai and Ningbo Port workshop makes it convenient to delivery on time.
Our workshop