Xlpo Insulation Photovoltaic Cable Solar Cable 6mm 300mm2 PV Cable
Beschreibung
H1z2z2-K Photovoltaic PV Solar PV Cable Consruction:
Dirigent: Klasse 5 flexible tinned copper conductor
Isolierung: Halogen-free cross-linked compound
Sheath: Halogen-free cross-linked, flame retardant compound, Black
H1z2z2-K Photovoltaic PV Solar PV Cable Application
H1z2z2-K Photovoltaic PV Solar PV Cable Standards
DIN EN 50618, TüV 2 PfG 1169/08.2007
Fire-resistance performance: IEC 60332-1
Low smoke emission : EN/IEC 61034-2
Halogen free according to EN 50525-1, Annex B
Low corrosivity of gases according to EN 50267-2-2, IEC 60754-2
H1z2z2-K Photovoltaic PV Solar PV CableTechnical Character:
Working voltage:AC: 600/1000V DC: 900/1800v
Maxium Voltage:1.8KV
Test Voltage: 6.5kV AC
Arbeitstemperatur:-40-90 º C
Bending Radiu:
Fixed: 4 x overall diameter
Flexed: 5 x overall diameter
max. Conductor temperature: 120º C
Short-circuit max. Conductor temperature:250°C
Insulation resistance: 10 MΩ x km
H1z2z2-K Photovoltaic PV Solar PV Cable Parameter:
NEIN. of Cores×Nominal Cross Section | NEIN. of Stranding | Nominal Conductor Diameter | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diamater | Nominal Weight |
No.×mm2 | – | mm | mm | mm | mm | kg/km |
1×1,5 | 30/0.25 | 1.58 | 0.7 | 0.8 | 5.4 | 40 |
1×2.5 | 50/0.25 | 2.04 | 0.7 | 0.8 | 5.9 | 50 |
1×4.0 | 56/0.30 | 2.59 | 0.7 | 0.8 | 6.6 | 70 |
1×6.0 | 84/0.30 | 3.17 | 0.7 | 0.8 | 7.4 | 80 |
1×10 | 78/0.40 | 4.07 | 0.7 | 0.8 | 8.8 | 130 |
1×16 | 128/0.40 | 5.22 | 0.7 | 0.9 | 10.1 | 200 |
1×25 | 199/0.40 | 6.51 | 0.9 | 1 | 12.5 | 290 |
1×35 | 279/0.40 | 7.71 | 0.9 | 1.1 | 14 | 400 |
1×50 | 396/0.40 | 9 | 1 | 1.2 | 16.3 | 550 |
1×70 | 360/0.50 | 10.8 | 1.1 | 1.2 | 18.7 | 750 |
1×95 | 475/0.50 | 12.6 | 1.1 | 1.3 | 20.8 | 970 |
1×120 | 608/0.50 | 14.2 | 1.2 | 1.3 | 22.8 | 1220 |
1×150 | 756/0.50 | 15.8 | 1.4 | 1.4 | 25.5 | 1510 |
1×185 | 925/0.50 | 17.4 | 1.6 | 1.6 | 28.5 | 1850 |
1×240 | 1221/0.50 | 20.4 | 1.7 | 1.7 | 32.1 | 2400 |
Current Carrying Capacity
Cross Section | AWG | Maximum Conductor Resistance at 20C | Maximum insulation Resistance at 20C | Maximum insulation Resistance at 90C | Current Carrying Capacity | ||
Single cable free in air | Single cable on surfaces | 2 loaded cables adjacent on surfaces | |||||
mm2 | – | Ω | MΩ.km | MΩ.km | EIN | EIN | EIN |
1.5 | 16 | 13.7 | 859 | 0.859 | 30 | 29 | 24 |
2.5 | 14 | 8.21 | 691 | 0.691 | 41 | 39 | 33 |
4 | 12 | 5.09 | 579 | 0.579 | 55 | 52 | 44 |
6 | 10 | 3.39 | 499 | 0.499 | 70 | 67 | 57 |
10 | 8 | 1.95 | 424 | 0.424 | 98 | 93 | 79 |
16 | 6 | 1.24 | 342 | 0.342 | 132 | 125 | 107 |
25 | 4 | 0.795 | 339 | 0.339 | 176 | 167 | 142 |
35 | 2 | 0.565 | 287 | 0.287 | 218 | 207 | 176 |
50 | 1/0 | 0.393 | 268 | 0.268 | 276 | 262 | 221 |
70 | 2/0 | 0.277 | 247 | 0.247 | 347 | 330 | 278 |
95 | 3/0 | 0.21 | 220 | 0.22 | 416 | 395 | 333 |
120 | 4/0 | 0.164 | 211 | 0.211 | 488 | 464 | 390 |
150 | 300 kcmil | 0.132 | 206 | 0.206 | 566 | 538 | 453 |
185 | 350 kcmil | 0.108 | 200 | 0.2 | 644 | 612 | 515 |
240 | 450 kcmil | 0.082 | 198 | 0.198 | 775 | 736 | 620 |