Contactor LC1 Cjx2 Series AC Contactor 220V Coil AC Contactor Factory
N º de Modelo.
CSCJX2-1801
Marca comercial
Changsong
Paquete de transporte
Standard Export Packing
Especificación
LC1-D
Origen
Zhejiang, China
Código hs
8536490000
Descripción
CJX2 series AC contactor are used for controlling 3-phase motors and generally for controlling power circuits,and for many other applications such as isolation, capacitor switching and lighting.
Modelo | CJX2-09 | CJX2-12 | CJX2-18 | CJX2-25 | CJX2-32 | CJX2-40 | CJX2-50 | CJX2-65 | CJX2-80 | CJX2-95 | ||
Number of the contacts | 3P+NO / 3P+NC | 3P+NO+NC | ||||||||||
Rated conventional heating current (A) AC-1 | 20 | 20 | 32 | 40 | 50 | 60 | 80 | 80 | 110 | 125 | ||
Rated operational current (A) | 400(380V) | AC-3 | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 |
AC-4 | 3.5 | 5 | 7.7 | 8.5 | 12 | 18.5 | 24 | 28 | 37 | 44 | ||
690(660V) | AC-3 | 6.6 | 8.9 | 12 | 18 | 21 | 34 | 39 | 42 | 49 | 49 | |
AC-4 | 1.5 | 2 | 3.8 | 4.4 | 7.5 | 9 | 12 | 14 | 17.3 | 21.3 | ||
Rated insulation voltage V( C.A.) | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | ||
Power of controlled 3-phase cage motor (AC-3) | kW | 230(220)V AC | 2.2 | 3 | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 25 |
400(380)V AC | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | ||
460V AC | 4 | 5.5 | 7.5 | 11 | 15 | 22 | 25 | 37 | 45 | 45 | ||
690(660)V AC | 5.5 | 7.5 | 9 | 15 | 18.5 | 30 | 33 | 37 | 45 | 45 | ||
hp | 200V AC | 3 | 5 | 7.5 | 7.5 | 10 | 15 | 15 | 20 | 25 | 30 | |
240V AC | 3 | 5 | 7.5 | 10 | 15 | 20 | 20 | 25 | 30 | 30 | ||
460V AC | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | 40 | 40 | 50 | ||
600V AC | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | 40 | 40 | 50 | ||
Operating frequency (operations/h) | Electrical | AC-3 | 1200 | 1200 | 1200 | 1200 | 600 | 600 | 600 | 600 | 600 | 600 |
AC-4 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | ||
Mechanical | ||||||||||||
Electrical life (1*104 operations) | AC-3 | 100 | 100 | 100 | 100 | 80 | 80 | 60 | 60 | 60 | 60 | |
AC-4 | 20 | 20 | 20 | 20 | 20 | 15 | 15 | 15 | 10 | 10 | ||
Mechanical life (1*104 operations) | 1000 | 1000 | 1000 | 1000 | 800 | 800 | 800 | 800 | 600 | 600 |
AC coil | Coil voltage (V) (50Hz,60Hz,50/60Hz) | 24,36,42,48,110,127,220,230,240,380,400,415,440,480,600 | |||||||||
Operation range | Operation voltage | (85%~110% ) Us | |||||||||
Drop-out voltage | (20%~75% ) Us | ||||||||||
Coil power | 50Hz | In-rush (VA) | 70 | 110 | 110 | 110 | 200 | 200 | 200 | 200 | 200 |
Sealed (VA) | 8 | 11 | 11 | 11 | 20 | 20 | 20 | 20 | 20 | ||
60Hz | In-rush (VA) | 80 | 115 | 115 | 115 | 200 | 200 | 200 | 200 | 200 | |
Sealed (VA) | 8 | 11 | 11 | 11 | 20 | 20 | 20 | 20 | 20 | ||
Energía (W) | 1.8~2.7 | 3~4 | 3~4 | 3~4 | 6~10 | 6~10 | 6~10 | 6~10 | 6~10 |